Laurel Electronics for Digital Panel Meters, Counters, Timers, Transmitters, Digital Displays

Digital Panel Meters - Counters - Timers - DIN Rail Transmitters - Large Digit Displays

   

Price List  |  Distributors  |  Search  |  Inquiry  |  Home

TS6 Serial-to-Analog DIN Rail Transmitter
 Converts serial data to a scaled analog signal.
 

Laurel TS6 Serial-to-Analog DIN Rail Transmitter

CE Mark     RoHS Mark

 
Features

  • RS-232 or RS-485 serial input.
  • Choice of 3 protocols: Modbus RTU, Modbus ASCII, or Laurel ASCII.
  • Able to retrieve data from long character strings.
  • Data rates from 300 to 19,200 bps.
  • Isolated 4-20 mA or 0-10V transmitter output, user selectable.
  • Analog output resolution: 0.025% of span (12 bits).
  • Analog output accuracy: ±0.05% of span.
  • Update rate to 60/sec.
  • DIN rail mount package only 22.5 mm (0.89") thick.
  • Powered by AC or DC.
  • Detachable screw-clamp connectors.
  • Powered by 95-240 Vac ±10% (standard) or low voltage AC or DC (optional).
  • Easy setup using PC-based Instrument Setup Software.
  • Optional dual solid state relays for alarm or control.

Description

Signal Inputs and Outputs of Laurel TS6 Serial-to-Analog DIN Rail Transmitter

The Laureate TS6 serial input to analog output transmitter accepts RS-232 or RS-485 serial data with Modbus or Laurel ASCII Protocols, and converts it to an isolated, scalable 4-20 mA or 0-10V analog output signal. The unit fits on a 35 mm DIN rail and is only 22.5 mm (0.89") thick. It is normally powered by AC (95-240 Vac ±10%), but can optionally be powered by low voltage AC or DC. All electrical connections are via detachable screw-clamp plugs.

Serial Data Input

One three-screw-terminal connector accepts RS-232 or RS-485 serial data, as selected via jumpers on the main board. Data rates are selectable as 300, 600, 1200, 2400, 4800, 9600 or 19200 bps. The RS-232 interface is suitable for short cable runs and point-to-point communications. The RS-485 interface is compliant with the EIA/TIA-485 standard and supports multiple addressable devices on the same data line using the Modbus protocol or Laurel ASCII Protocol. Modbus implementation is fully compliant with Modbus over Serial Line Specification V1.0 (2002) in RTU or ASCII, half duplex (2-wire) operation, with up to 247 digital addresses.

Selectable Data Retrieval

The Laureate serial-to-analog transmitter is able to retrieve digital data from long character strings. You can specify character positions, start and stop ASCII characters, how many characters to skip, and how many characters to process.

Analog Transmitter Output

The analog output is selectable as 0-10V or 4-20 mA (also scalable for 0-20 mA). All selections provide 12-bit (0.025%) resolution of the output span and are ultra-linear to within one bit. Accuracy is ±0.05% of output span. Output isolation from signal, power and serial communication grounds is provided by a separate on-board transmitter power supply, thereby eliminating potential problems caused by ground loops. The supply can an drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into 5K ohm (or higher) load for 2 mA compliance.

Easy to Set Up and Install

Transmitter programming is via a three-terminal RS-232 port using Laurel's PC-based Instrument Setup Software. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL03).

Laurel's transmitters and meters can be part of PC-based data logging systems using Laurel's Datalogging Software, which operates under the Laurel ASCII Protocol.

Specifications
Laureate TS6 Serial-to-Analog DIN Rail Transmitter

RS-232 Input Interface
Data Rates
Devices on RS232 line
Connector
Supported Protocols
Isolation

300, 600, 1200, 2400, 4800, 9600, 19200 bps
1 (point-to-point, short distances)
Three detachable screw-clamp plugs: RXD, TCD, common
Modbus or Laurel ASCII
250V rms from power and analog output continuous,
2.3 kV rms per 1 min test.

RS-485 Input Interface
Cabling
Data Rates
Devices o RS485 line
Connector
Standards Compliance
Supported Protocols
Isolation
Half duplex (2-wire)
300, 600, 1200, 2400, 4800, 9600, 19200 bps
32 max
Three detachable screw-clamp plugs: D0, D1, common
EIA/TIA-485
Modbus or Laurel ASCII
250V rms from power and analog output continuous,
2.3 kV rms per 1 min test.
Modbus Protocol
Type
Standards Compliance
Digital Addresses
RTU or ASCII.
Modbus over Serial Line Specification V1.0 (2002)
247 max
Laurel ASCII Protocol
Type
Digital Addresses
ASCII.
31 max
Serial Input Electrical Protection
ESD Protection
EMI Immunity
EFT Protection
Short Circuit Protection
15 kV per IEC 1000-4-2
10 V/m per IEC 1000-4-3
2 kV per IEC 1000-4-4
Continuous
Analog Output
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Isolation
0-20 mA or  0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
12 bits (4,096 steps)
±0.05% of output span
250V rms from power and serial I/O continuous,
2.3 kV rms per 1 min test.
Dual Relay Output (optional)
Relay Type
Load rating
Two solid state relays, SPST, normally open, Form A
120 mA at 130 Vac or 170 Vdc, 28 ohms in series
Power, Electrical & Setup
Power to Transmitter
 
Transmitter Setup
95-240 Vac ±10% or 90-300 Vdc (DC operation not UL approved)
9-30 Vac or 10-48 Vdc (low voltage power option)
Via RS-232 from PC using Instrument Setup Software and CBL03 cable.
Mechanical
Case Dimensions
Case Mounting
Electrical Connections
120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Detachable screw-clamp plugs
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
0°C to 70°C
-40°C to 85°C
95% at 40°C, non-condensing

Pinout
Laureate Serial Input, Analog Output, DIN Rail Transmitter
Shown with optional dual relay outputs.

Pinout, Laurel TS6 Serial-to-Analog DIN Rail Transmitter

Ordering Guide
Laureate Serial Input, Analog Output, DIN Rail Transmitter
 Click on the radio buttons to build a model number with pricing.

  Quantity
Transmitter
Type
TS6   Serial input transmitter, 4-20 mA, 0-20 mA or 0-10V output. $175
Power 95-240 Vac ±10%
Isolated 12-30 Vac or 10-48 Vdc.
NC
$30
Setpoint
Output
None.
Isolated Dual Solid State Relays.
NC
$30
Accessories CBL03  RS-232 cable, TS6 to computer.
CBL02
  USB to RS-232 cable adapter.
$19
$39
 
Configured model number TS600
Configured price per model $175
Quantity 1
Extended price $175
 

 

Price List  |  Distributors  |  Search  |  Inquiry  |  Privacy  |  Home

  
Laurel Electronics, Inc.
Industrial Instrumentation & Displays
3183-G Airway Avenue
Costa Mesa, CA 92626, USA
Tel:      
Fax:
     
(714) 434-6131
(714) 434-3766

  