LTA-VF
4-20 mA Current Transmitter &
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
![]()
|
![]()
Description The Laureate LTA-VF process signal input totalizing transmitter accepts 0-1 mA, 4-20 mA or 0-10V signals from flow meters and other transducers, such as watt meters, to track rate or totalized rate.
Three analog transmitter settings are jumper selectable: 4-20 mA, 0-20 mA or 0-10V. All selections provide 16-bit (0.0015%) resolution of output span and 0.02% output accuracy. The output tracks the reading from -99,999 to +99,999 counts that would be transmitted digitally. For process signals, this reading has a rated accuracy of ±0.01% of full scale input and can be scaled in software. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher) load for 2 mA compliance. Standard features of Model LTA-VF include:
Easy Transmitter programming is via Laurel's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL04). |
![]()
Specifications
LTA-VF 4-20 mA Transmitter & Totalizer
for 0-1 mA, 4-20 mA or 0-10V Signals
| Analog Input | 0-1 mA | 4-20 mA | 0-10 V |
|
Input resistance Max current or voltage |
182 ohms 37 mA |
9 ohms 160 mA |
1 Mohm 600 V |
|
Input Resolution Span Tempco Zero Tempco Accuracy at 25°C Read Rate |
6 digits |
||
| Analog Output | |||
|
Output Levels Compliance, 4-20 mA Compliance, 0-10V Output Resolution Output Accuracy Output Update Rate Output Isolation |
4-20 mA and 0-10 Vdc (selectable) 10V ( 0-500 ohm load ) 2 mA ( 5 kOhm load ) 12 bits (4,096 steps) ±0.05% of output span 25/sec 250V rms working, 2.3 kV rms per 1 minute test |
||
| Transducer Excitation Output (standard) | |||
|
Jumper Selection 1 Jumper Selection 2 Jumper Selection 3 |
10V @ 60 mA, isolated to 50V from signal ground 5V @ 50 mA, isolated to 50V from signal ground 15V @ 60 mA, non-isolated |
||
| Dual Relay Output (optional) | |||
|
Relay Type Load rating |
Two solid state relays, SPST, normally open,
Form A 120 mA at 130 Vac or 170 Vdc, 28 ohms in series |
||
| Power Input | |||
|
Standard power Low power option Frequency Power Isolation |
95-240 Vac ±10% or 90-300 Vdc (DC operation not UL approved) 12-30 Vac or 10-48 Vdc DC or 47-63 Hz 250V rms working, 2.3 kV rms per 1 min test |
||
| Mechanical | |||
|
Case Dimensions Case Mounting Electrical Connections |
120 x 101 x 22.5 mm 35 mm rail per DIN EN 50022 Detachable screw clamp plug connectors |
||
| Environmental | |||
|
Operating Temperature Storage Temperature Relative Humidity |
0°C to
70°C -40°C to 85°C 95% at 40°C, non-condensing |
||
![]()
Pinout
LTA-VF 4-20 mA Transmitter & Totalizer
for 0-1 mA, 4-20 mA or 0-10V Signals

![]()
Ordering
Guide
LTA-VF 4-20 mA Transmitter & Totalizer
for 0-1 mA, 4-20 mA or 0-10V Signals
Click
on the radio buttons to build a model number with pricing.
|
Resource Pages |
|