4-20 mA Current Output
RTD Temperature Transmitter
 Exceptional linearity & accuracy at high update rates.
DIN Rail mounted, digitally programmable.

4-20 mA Current Transmitter for RTD Temperature

RoHS Mark

Made in California

Standard Features

  • Factory calibrated for 100Ω platinum, 10Ω copper & 120Ω nickel RTDs
  • 2, 3 or 4-wire RTD connection with lead resistance compensation
  • Upscale or downscale open sensor indication
  • User selectable spans from entire RTD range down to 15.0°
  • Output update rate to 60/sec
  • Output resolution:  0.0015% of span (16 bits)
  • Switching power supply for 85-264 Vac
  • DIN rail mount housing only 22.5 mm wide
  • Detachable screw-clamp connectors
  • Dual solid state relays for alarm or control, isolated
  • RS232 or RS485 serial communications, isolated
  • Universal AC power, 85-264 Vac
  • Easy setup with PC-based Instrument Setup Software
  • Priced at only $235 (basic temperature transmitter)
    Options:
  • Low voltage power, 10-48 Vdc or 12-32 Vac

Description

The Laureate 4-20 mA RTD temperature transmitter provides a linearized, highly accurate, stable and repeatable transmitter output for 100 ohm platinum, 10 ohm copper and 120 ohm nickel RTDs. Pt 100 platinum RTDs can have a DIN alpha of 0.00385 or ANSI alpha of 0.00392. The RTD type and temperature range, specified in °C or °F, are user-selectable. The temperature range can be as wide as the entire span of the RTD type or as narrow as 150 counts (such as 15.0°), limited only by considerations of electrical noise and digital filtering time constants.

RTD signal conditioner boardDigital calibration of all RTD ranges is performed the factory, with calibration data stored in EEPROM on the signal conditioner board. This allows signal conditioner boards and ranges to be changed in the field with no need for recalibration. Open sensor indication is standard and may be set up to indicate either upscale or downscale. RTD excitation is provided by the transmitter. RTD connections can be of the 2-, 3- or 4-wire type. With 3- and 4-wire connections, the transmitter automatically compensates for lead resistance of the sensor.

Fast read rate at up to 50 or 60 conversions per second while integrating the signal over a full power line cycle is provided by Concurrent Slope (Pat 5,262,780) analog-to-digital conversion. High read rate is ideal for peak or valley capture and for real-time computer interface and control.

Three analog transmitter settings are jumper selectable: 4-20 mA, 0-20 mA or 0-10V. All selections provide 16-bit (0.0015%) resolution of output span and 0.02% output accuracy. The output tracks the reading from -99,999 to +99,999 counts that would be transmitted digitally. For DC signals, this reading has a rated accuracy of ±0.01% of full scale input and can be scaled in software. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher) load for 2 mA compliance.

Standard features of Laureate temperature transmitters include:

  • Analog transmitter output, 16-bit, user scalable and isolated. User selectable 4-20 mA, 0-20 mA or 0-10V levels.
  • Serial communications, isolated. User selectable RS232 or RS485, half or full duplex, Modbus or Laurel ASCII protocol.
  • Dual solid state relays for control or alarm, isolated. Rated 120 mA at 130 Vac or 170 Vdc.
  • Universal AC power supply for 85-264 Vac. Low voltage power of 10-48 Vdc or 12-32 Vac is optional.

Easy Transmitter programming is via Laurel's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL04).

Specifications
Laureate 4-20 mA RTD Temperature Transmitter

RTD
Metal
Alpha R at
0°C
R at top
of range
Excitation
Current
Range Conformity
Error
Platinum 0.003850
(DIN)
100Ω 390.48Ω
at 850°C
256 μA -200°C to +850°C
-328°F to +1562°F
±0.03°C
±0.05°F
Platinum 0.003902
(ANSI)
100Ω 394.36Ω
at 850°C
256 μA -200°C to +850°C
-328°F to +1168°F
±0.04°C
±0.07°F
Nickel 0.00672 120Ω 380.31Ω
at 260°C
256 μA -80°C to +260°C
-112°F to +500°F
±0.05°C
±0.09°F
Copper 0.00427 9.035Ω 19.116Ω
at 260°C
5.0 mA -97°C to +260°C
-143°F to +500°F
±0.05°C
±0.09°F
 
RTD Input

Calibration, Pt 100 DIN
Calibration, Pt 100 ANSI

Configuration
Excitation current
Overall accuracy
Span tempco
Zero tempco
Sensor lead resistance
   tempco per conductor
Over-voltage protection
Open sensor indication

IEC 751 (IPTS-68)
NIST Monograph 126
2, 3 or 4-wire connection
0.2 mA
±0.01 of full scale ±2 counts
±0.003% of reading/ºC
±0.03 deg/deg
2-wire, 10 mdeg/W/deg up to 10 W
3 & 4-wire, 10 mdeg/W/deg up to 100 W
125 Vac
0 mA or > 20mA output, selectable

Analog Output (standard)

Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation

4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load or higher)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test

Dual Relay Output (standard)

Relay Type
Load Rating

Two solid state relays, SPST, normally open, Form A
130 mA at 140 Vac or 180 Vdc

Serial Communications (standard)

Signal Types
Data Rates
Output Isolation
Serial Protocols
Modbus Modes
Modbus Compliance
Digital Addressing

RS232 (default) or RS485, 2 or 4-wire (user selectable)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII
RTU or ASCII
Modbus over Serial Line Specification V1.0 (2002)
247 Modbus addresses.
Up to 32 devices on an RS485 line w/o a repeater.

Power Input

Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption

85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical

Mechanical

Dimensions
Mounting
Electrical Connections

120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors

Environmental

Operating Temperature
Storage Temperature
Relative Humidity
Cooling Required

0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan.

Pinouts
Laureate 4-20 mA RTD Temperature Transmitter

Pinout of RTD temperature transmitter

4-wire hookup of RTD signal conditioner board

RTD hookup can be via 2, 3 or 4 wires to the J5 connector. The transmitter applies an excitation current of 196 μA (Pt 100 and Ni 120) or 5 mA (Cu 10).
In 4-wire hookup, different pairs of leads are used to apply the excitation current and sense the voltage drop across the RTD, so that the IR drop across the excitation leads is not a factor.

3-wire hookup of RTD signal conditioner board

In 3-wire hookup, the transmitter senses the combined voltage drop across the RTD plus two excitation leads. It also senses the voltage drop across one excitation lead, and then subtracts twice this voltage from the combined total. This technique effectively subtracts all lead resistance and compensates for ambient temperature changes if the two excitation leads are identical.

2-wire hookup of RTD signal conditioner board

In 2-wire hookup, the transmitter senses the combined voltage drop across the RTD and both lead wires. The voltage drop across the lead wires can be measured by shorting out the RTD during transmitter setup, and this voltage is then automatically subtracted from the combined total. However, changing resistance of the lead wires due to ambient temperature changes will not be compensated.

Operation as a Fast ON/OFF Controller or Supervisory Monitor

Temperature controller operation of Laureate temperature meters and transmittersWith the optional dual solid state relay output option, which has a typical response time of only 17 ms, Laureate temperature meters and transmitters can serve as extremely fast and accurate ON/OFF controllers for closed-loop temperature control. They can also serve as supervisory process monitors and provide alarms or shutoffs when processes exceed normal limits.

Multiple setpoint operating modes are individually selectable for each relay, as explained in the dual-setpoint controller page. Relay duty cycles and chatter can be minimized with programmable hysteresis and time delays. A band deviation operating mode can be selected for each relay, where an alarm is generated whenever the reading is a selected number of counts above or below the setpoint. The relay modes have to be non-latching, since 4-20 mA temperature transmitters do not offer external reset.

Ordering Guide
Laureate 4-20 mA RTD Temperature Transmitter
 Click on the radio buttons to build a model number with pricing (shown below the Ordering Guide).

Quantity
Transmitter
Type
LTA  Laureate 4-20 mA Transmitter $235
Main Board Standard Main Board NC
Power Isolated 85-264 Vac
Isolated 10-48 Vdc or 12-32 Vac
NC
$30
Relay
Output
None.
Isolated Dual Solid State Relays
NC
NC
RTD
Input
P385C  Pt 100 DIN RTD, -202°C to 850°C
P385F  Pt 100 DIN RTD, -331°F to 1562°F
P392C  Pt 100 ANSI RTD, -202°C to 631°C
P392F  Pt 100 ANSI RTD, -331°F to 1168°F
N672C  Ni 120 RTD, -100°C to +260°C
N672F  Ni 120 RTD, -148°F to +500°F
C427C  Cu 10 RTD, -100°C to +260°C
C427F  Cu 10 RTD, -148°F to +500°F
 NC

Note: The same signal conditioner board can be user configured for all RTD types listed and °C or °F, as well as for resistance measurement.

Accessories CBL04  RS-232 cable, LTA to computer or USB adapter
CBL02
  USB to RS-232 cable adapter
$19
$39
 

Configured model number

LTA200P385C

Configured price per model

$235

Quantity

1

Extended price

$235

 

 

  

Products by Type

  

Meters by Application

  

Resource Pages