4-20 mA Current Output Transmitter
for Load Cell or Microvolt Input

 Powers up to four 350 ohm load cells in parallel. DIN Rail mounted.
Digitally programmable. Exceptional accuracy at high update rates.

4-20 ma transmitter,microvolt signals,35 mm DIN rail,transmitters

 RoHS Mark
Made in California

Standard Features

  • 20, 50, 100, 250 & 500 mV full-scale range
  • 4 or 6-wire hookup to avoid supply and lead resistance effects.
  • Isolated excitation output, 120 mA at 10V, to power up to four 350 ohm load cells in parallel
  • Digital span adjust from 0 to ±99,999
  • Digital zero adjust from -99,999 to +99,999
  • 4-20 mA, 0-20 mA or 0-10V transmitter output, jumper selectable, isolated
  • Output resolution:  0.0015% of span (16 bits)
  • Output accuracy: ±0.02% of span
  • Output update rate to 60/sec
  • Switching supply for 85-264 Vac
  • Easy setup with PC-based Instrument Setup Software
  • DIN rail mount housing only 22.5 mm wide
  • Detachable screw-clamp connectors
  • Dual solid state relays for alarm or control, isolated
  • RS232 or RS485 serial communications, isolated
  • Universal AC power, 85-264 Vac
  • Priced at only $290 (basic load cell transmitter)
    Options:
  • Extended main board for custom curve linearization & rate from successive readings
  • Low voltage power, 10-48 Vdc or 12-32 Vac

Description

The Laureate 4-20 mA output, load cell or microvolt input transmitter is designed for use with load cells, strain gauges and microvolt input signals where exceptional sensitivity and stability are required. A most sensitive full-scale input range ±20 mV can be scaled internally to ±99,999 counts. The selected input range for the full 0-20 mA output span can be as wide as ±99,999 counts or as narrow as 150 counts, limited only by considerations of electrical noise and time constants of the programmable moving average digital filter.

A built-in, isolated, 10V, 120 mA excitation supply can power up to four 350-ohm load cells in parallel. Load cell connection can be via 4 or 6 wires. With 4-wire load connection, the transmitter operates in a ratiometric mode to eliminate errors due to supply variations. With 6-wire load connection, it also compensates for variation in resistance of the transducer leads, thereby allowing long cable runs.

Fast read rate at up to 50 or 60 conversions per second while integrating the signal over a full power line cycle is provided by Concurrent Slope (Pat 5,262,780) analog-to-digital conversion. High read rate is ideal for peak or valley capture and for real-time computer interface and control.

Digital signal filtering modes are selectable for stable readings in electrically noisy environments. The internal digital readings and analog output can be separately selected to be either unfiltered or filtered.

  • An unfiltered selection updates after each conversion for fastest response, up to 60/sec, while integrating the input signal over a full power cycle. Fast read rate provides true peak and valley readings and aids in control applications.
  • A batch average filter selection averages each 16 conversions for an update every 1/4 sec.
  • An adaptive moving average filter selection provides a choice of 8 time constants from 80 ms to 9.6 s. When a significant change in signal level occurs, the filter adapts by briefly switching to the shortest time to follow the change, then reverts back to its selected time constant. Another choice is Auto, which provides an automatic time constant selection based on the signal noise characteristics.

Three analog transmitter settings are jumper selectable: 4-20 mA, 0-20 mA or 0-10V. All selections provide 16-bit (0.0015%) resolution of output span and 0.02% output accuracy. The output tracks the reading from -99,999 to +99,999 counts that would be transmitted digitally. For DC signals, this reading has a rated accuracy of ±0.01% of full scale input and can be scaled in software. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher) load for 2 mA compliance.

Standard features of Model LTA-WM include:

  • Analog transmitter output, 16-bit, user scalable and isolated. User selectable 4-20 mA, 0-20 mA or 0-10V levels.
  • Serial communications, isolated. User selectable RS232 or RS485, half or full duplex, Modbus or Laurel ASCII protocol.
  • Dual solid state relays for control or alarm, isolated. Rated 120 mA at 130 Vac or 170 Vdc.
  • Transducer excitation output, isolated. User selectable 5V@100 mA, 10V@120 mA or 24V@50 mA.
  • Universal AC power supply for 85-264 Vac.

Easy Transmitter programming is via Laurel's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL04).

Load Cell Transmitter Connections
  

4-wire load cell bridge connection of load cell transmitter

In 4-wire connection, the excitation and sense lines are tied together. The transmitter can make ratiometric corrections for supply voltage variations, but does not compensate for variations in lead resistance. This connection is often used with short cable runs.

4-wire load cell bridge connection of load cell transmitter

In 6-wire connection, the sense lines are separate from the excitation lines, thereby eliminating effects due to variations in lead resistance. This allows long cable runs in outdoor environments with temperature extremes.

Up to six 350-ohm load cell bridges connected in parallel to a load cell transmitter

For large scales, up to four 350 ohm load cells in parallel can be powered by a single Laureate transmitter at 10V, 120 mA excitation. The excitation and sense points of the four bridges are connected in parallel through a summing box.

Specifications
Laureate 4-20 mA Transmitter for Load Cell or Microvolt Input

Analog Input

Range Resolution Input Ohms

Load Cell Input
 
 
 
 

     ±20.000 mV      
±50.0000 mV
±100.00 mV
±250.00 mV
±500.00 mV
-99,999 to +99,999
zero adjust.

 

0 to ±99,999
span adjust.
1 Gohm

Microvolt Input
 
 
 
 

  ±20.000 mV 
±50.0000 mV
±100.00 mV
±250.00 mV
±500.00 mV
1 µV
2.5 µV
5.0 µV
12.5 µV
25 µV
1 Gohm

Input Resolution
Input Accuracy
Update Rate, Max
Max Applied Voltage

16 bits (65,536 steps)
±0.01% of full scale ± 2 counts
50/sec at 50 Hz, 60/sec at 60 Hz.
100 V

Transducer Excitation Output (standard)

Output Levels
Output Isolation

5V@100 mA, 10 @120 mA, 24V@50 mA (jumper selectable)
50V from signal ground

Analog Output (standard)

Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation

4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load or higher)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test

Dual Relay Output (standard)

Relay Type
Load Rating

Two solid state relays, SPST, normally open, Form A
130 mA at 140 Vac or 180 Vdc

Serial Communications (standard)

Signal Types
Data Rates
Output Isolation
Serial Protocols
Modbus Modes
Modbus Compliance
Digital Addressing

RS232 (default) or RS485 (half or full duplex)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII
RTU or ASCII
Modbus over Serial Line Specification V1.0 (2002)
247 Modbus addresses.
Up to 32 devices on an RS485 line w/o a repeater.

Power Input

Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption

85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical, 3W with max excitation output

Mechanical

Dimensions
Mounting
Electrical Connections

120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors

Environmental

Operating Temperature
Storage Temperature
Relative Humidity
Cooling Required

0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan.

Pinout
Laureate 4-20 mA Transmitter for Load Cell or Microvolt Input

pin out analog of 4-20 transmitter

Ordering Guide
 Laureate 4-20 mA Transmitter for Load Cell or Microvolt Input
 Click on the radio buttons to build a model number with pricing (shown below the Ordering Guide).  

 Quantity
Transmitter
Type
LTA   Laureate 4-20 mA Transmitter $235
Main Board Standard Main Board
Extended Main Board
NC
$40
Note: Extended allows custom curve linearization and rate from successive readings.  
Power Isolated 85-264 Vac
Isolated 12-32 Vac or 10-48 Vdc
NC
$30
Relay
Output
None
Isolated Dual Solid State Relays
NC
NC
Signal Input Load Cells (6-wire ratio)
WM    Default Scaling. 0-20 mV in = 4-20 mA out
WM1  Custom Scaling
 
$55

In the write-in field of your invoice, specify min input, min output; max input, max output.

Accessories CBL04  RS-232 cable, LTA to computer or USB adapter
CBL02
  USB to RS-232 cable adapter
$19
$39
 

Configured model number

LTA200WM

Configured price per model

$290

Quantity

1

Extended price

$290

 

 

  