LTA-FR
4-20 mA Current Transmitter
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
![]() |
|
Standard Features
|
![]()
Description The Laureate LTA-FR frequency, rate and period transmitter accepts two independently scalable input channels from a wide range of pulse sources, such as NPN or PNP proximity switches, contact closures, digital logic, magnetic pickups down to 12 mV, or AC voltages to 250 Vac. Input frequencies can range from 0.005 Hz to 1 MHz. The transmitter output can be selected as 4-20 mA, 0-20 mA or 0-10V, and is isolated to avoid ground loops. Applications include AC line frequency, RPM or speed from proximity switch inputs, and flow from turbine flow meter inputs.
The update rate of the transmitter output is a programmed gate time + 30 ms + 0-2 signal periods. For a 60 Hz signal, the update rate would be 20 per second. Such fast update rates are ideal for alarm and control. Standard features of Model LTA-FR include:
Easy Transmitter programming is via Laurel's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL04). |
![]()
Specifications
LTA-FR 4-20 mA Transmitter for
Pulse,
Frequency, Rate or Period Input
| Analog Input | |
| Types Grounding Channel A Frequency Channel B Frequency Minimum Signal Maximum Signal Noise Filter Contact Debounce Time Base Accuracy |
AC,
pulses from NPN, PNP transistors, contact closures, |
| Analog Output (standard) | |
|
Output Levels Compliance, 4-20 mA Compliance, 0-10V Output Resolution Output Accuracy Output Update Rate Output Isolation |
4-20 mA and 0-10 Vdc (selectable) 10V ( 0-500 ohm load ) 2 mA ( 5 kOhm load ) 12 bits (4,096 steps) ±0.05% of output span Programmed gate time + 30 ms + 0-2 signal periods 250V rms working, 2.3 kV rms per 1 minute test |
| Sensor Excitation Output (standard) | |
|
Output levels Output isolation |
5V@100 mA, 10V@120 mA, 24V@50 mA (jumper
selectable) 50V from signal ground |
| Dual Relay Output (standard) | |
|
Relay Type Load rating |
Two solid state relays, SPST, normally open,
Form A 120 mA at 130 Vac or 170 Vdc, 28 ohms in series |
| Serial Communications (standard) | |
|
Signal Types Data Rates Output Isolation Serial Protocols Modbus Modes Modbus Compliance Digital Addressing |
RS232 or RS485 (half or full duplex) 300, 600, 1200, 2400, 4800, 9600, 19200 baud 250V rms working, 2.3 kV rms per 1 min test Modbus RTU, Modbus ASCII, Laurel ASCII RTU or ASCII Modbus over Serial Line Specification V1.0 (2002) 247 Modbus addresses. Up to 32 devices on an RS485 line w/o a repeater. |
| Power Input | |
|
Standard power Low power option Frequency Power Isolation |
95-240 Vac ±10% or 90-300 Vdc (DC operation not UL approved) 12-30 Vac or 10-48 Vdc DC or 47-63 Hz 250V rms working, 2.3 kV rms per 1 min test |
| Mechanical | |
|
Case Dimensions Case Mounting Electrical Connections |
120 x 101 x 22.5 mm 35 mm rail per DIN EN 50022 Detachable screw clamp plug connectors |
| Environmental | |
|
Operating Temperature Storage Temperature Relative Humidity |
0°C to
70°C -40°C to 85°C 95% at 40°C, non-condensing |
![]()
| Application Examples of Frequency / Rate Meters | |
AC Line Frequency |
|
|
|
Laureate frequency meters or transmitters will accept line voltages up to 250 Vac and display line frequency to 6-digit accuracy (50.0000 or 60.0000) in a few line cycles. Fast low frequency response is achieved by timing the period and taking its inverse. |
RPM and Speed |
|
|
|
he Laureate frequency meters or transmitters can sense the low-level signals from magnetic pickups or the NPN or PNP transistor output of active sensors. These can be powered directly by the meter. Display in RPM or units of speed is achieved by mathematically scaling the meter. |
Flow Rate and Simultaneous Total |
|
|
|
Laureate frequency meters or transmitters are compatible with all flow meters which generate pulses at a frequency proportional to flow rate. The Extended version can display scaled rate or total for the same input at the push of a button, and alarm from both the rate and total. The Extended version can also linearize flow transducers so as to extend their dynamic range. |
Combining Two Rates |
|
![]() |
Extended Laureate frequency meters or transmitters offers A+B, A-B and A/B arithmetic functions. A+B allows two input flows to be summed for total flow, while A-B allows outflow to be subtracted from inflow for net flow. Flow ratios aid in the proper mixing of ingredients |
Custom Curve Linearization |
|
![]() |
Extended Laureate frequency meters or transmitters can linearize the output turbine flow meters, which tend to be nonlinear on the low end. Linearizing improves the dynamic range and accuracy of turbine flow meters. |
System-level Capabilities |
|
The Laureate dual channel rate meters or transmitters can independently scale, display and alarm two pulse input channels. All signal or alarm data can further be transmitted via RS-232 or RS-485, including peak readings and arithmetic combinations of the two rates. |
|
![]()