Laureate™ Dual-Channel Pulse Input Totalizer
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
![]() |
|
|
![]() |
![]() |
|
![]()
Standard
Counter
All capabilities of the Standard Counter, plus:
Options:
|
![]()
Description
The six-digit counter display is capable of displaying any value from -999,999 to 999,999 with a programmable decimal point. Scaling allows direct readout in engineering units, such as gallons or cubic feet based on counts from a turbine flowmeter, or the count of cans based on the count of six-packs. The displayed channel (A or B) is selected via a front panel pushbutton. The totals are stored in non-volatile memory so as to be retained in the absence of power. The minimum recommended complementary option for the Laureate totalizer is the dual setpoint controller output board, which is available with either 8A relays or AC/DC solid state relays. An optional Extended counter version provides capabilities beyond those of the Standard counter:
The
FR dual-channel signal
conditioner accepts inputs from proximity switches with PNP or NPN output, TTL or CMOS
logic, magnetic pickups, contact closures, low-level outputs from turbine flow meters down
to 12 mV, and high-level AC line inputs up to 250 Vac.
Jumper
selections provide optimum operation for different sensor types and noise
conditions. A built-in isolated 5, 10, or 24 Vdc
excitation supply can power proximity switches and other sensors, and eliminate the need
for an external power supply.
Other Features and Options. Optional plug-in boards for communications and control include single or dual analog output boards, dual or quad relay boards, and serial communications boards. Laureates may be powered from 85-264 Vac or optionally from 12-32 Vac or 10-48 Vdc. The display is available with red or green LEDs. The 1/8 DIN case meets NEMA 4X (IP65) specifications from the front when panel mounted. Any setup functions and front panel keys can be locked out for simplified usage and security. |
![]()
|
Display |
|
|
Readout |
6 digits, 7-segment, 14.2 mm (0.56") |
|
Inputs |
|
|
Types |
AC,
pulses from NPN, PNP transistors, contact closures, |
|
Voltage, standard |
85-264 Vac or 90-300 Vdc (DC operation
not UL approved) |
|
Excitation Output (standard) |
|
|
5 Vdc |
5 Vdc ±5%, 100 mA |
|
Analog Output (optional) |
|
|
Output Levels |
4-20 mA, 0-20 mA, 0-10V, -10
to +10V (single-output option) |
|
Relay Outputs (optional) |
|
|
Relay
Types |
2 Form C
contact
relays or 4 Form A contact relays (NO) |
|
Serial Data I/O (optional) |
|
|
Board Selections |
RS232, RS485, Modbus RS485, USB, USB-to-RS485
converter |
|
Environmental |
|
|
Operating Temperature |
0°C
to 60°C |
|
Signal Connections |
|
|
|
|
![]()
Typical Applications
| Up/Down Totalizing | |
![]() |
Up/down totalizing is provided by a mode of the Extended counter where pulses are either added or subtracted on Channel A based on a direction input on Channel B. The counter can also be programmed so that counting by Channel A is inhibited by an input on Channel B. |
|
Combining Two Totals |
|
![]() |
A+B, A-B and A/B arithmetic functions are available with the Extended counter. A+B sums both totals, while A-B subtracts the outflow total from inflow total. The A/B ratio applied to total helps assure the proper mixing of components. |
|
Up or Down Counting with Preset |
|
![]() |
A single Laureate dual-channel counter will handle two repetitive fill operations by counting from zero up to a preset, or down from a preset to zero. A dual setpoint relay board is required. |
| Machine ON Time and Utilization | |
![]() |
An easy way to measure the ON time of machines is to count AC line cycles and scale the total to hours. To display machine utilization or duty cycle in percent, use the Extended counter. Connect Channel A to switched AC and Channel B to the AC line, and have the counter display the A/B ratio with a 100 multiplier. |
| Total and Rate Simultaneously | |
|
|
The Extended version of the Laureate dual channel counter can display scaled rate or total for the same channel at the push of a button, and alarm both the rate and total. The Extended version can also do curve linearization, thereby extending the working range and accuracy of flow transducers. |
| System-level Capabilities | |
![]() |
The Laureate dual channel totalizer can independently scale, display and alarm two totals, and the totals plus alarm data can be transmitted via RS-232 or RS-485. The displayed totals can also be transmitted as an isolated 4-20 mA or 0-10V analog output. The Extended version can further display and transmit arithmetic combinations of the two totals. |
![]()
Ordering
Guide
Laureate™ Dual-Channel Totalizer
Click on the radio buttons to build a model number with pricing (shown below the Ordering Guide).
|