Laureate™ Thermocouple
Temperature Panel Meter / Controller
High accuracy plus linearized transmitter
& control outputs

Standard Features
- Factory calibrated for
thermocouple types J, K, T, E, N, R, S
- Entire range of each
thermocouple in one scale
- Highly accurate
and
repeatable
- Selectable 1º or
0.1º resolution
- Selectable Celsius, Fahrenheit, Kelvin or
Rankin scales
- Selectable upscale or downscale open sensor
indication
- Up to 60 conversions per second
- Peak or valley display
- Universal AC power, 85-264 Vac
- NEMA 4X, 1/8 DIN case
- Certified to UL 61010C-1 (UL mark), EN
61010-1 (CE mark), and RoHS)
Options:
- Low voltage power: 10-48 Vdc or 12-32 Vac
-
2 or 4 output relays: electromechanical or
solid state
- Analog output: Isolated, 4-20 mA, 0-20 mA, 0-10V, -10
to +10V
- Serial communications: RS232, RS485, Modbus RS485,
USB, USB-to-RS485 converter
|

Description

The Laureate
thermocouple meter is factory calibrated for type J, K, T, E, N,
R and S thermocouples for exceptional accuracy and repeatability. The entire
span of each thermocouple type is presented in a single range. The
thermocouple type, unit of measure (°C or °F), resolution (1° or 0.1°),
and upscale or downscale open sensor indication are selectable from the
front panel or via the serial interface. Display in Kelvin or Rankin is selected by
offsetting the Celsius or Fahrenheit ranges. Cold junction compensation is
standard.
All ranges for all temperature sensor types
are digitally calibrated at the factory,
with calibration factors stored in an EEPROM on the signal conditioner
board. This allows temperatures sensors and signal conditioner boards to be
changed in the field without recalibrating the meter.
High read rates
at up to 60 or 50 conversions per second while integrating the signal
over a full power cycle are provided by Concurrent Slope (US Pat
5,262,780) analog-to-digital conversion. High
read rates are ideal for peak or valley capture, real-time computer interface, and control.
Peak and valley values are
automatically captured. These may be displayed via a front panel pushbutton command or a
control signal at the rear connector, or be transmitted as serial data.
Digital filtering is selectable for
electrically noisy environments,
including a batch averaging filter and an adaptive moving average filter
which provides a choice of 8 time constants from 80 ms to 9.6 s. When a significant
change in signal level occurs, that filter adapts by briefly switching to the shortest time
to follow the change, then reverts back to the selected time constant.
In a selectable Auto filter mode, the filter time constant is automatically
selected based on detected signal noise.
Designed for flexibility. Optional
plug-in boards for communications and control include an
analog output board, dual or
quad relay boards,
and serial communications boards. Laureates may be powered from
85-264 Vac or optionally
from 12-32 Vac or 10-48 Vdc. The display is available
with red or green LEDs. The 1/8 DIN case meets NEMA 4X (IP65) specifications from the front
when panel mounted. Any setup functions and front panel keys can be
locked out for simplified usage and security. |

Specifications
| TC Type |
Range |
Conformity Error |
| J |
-210°C to
+760°C (-347°F to +1400°F) |
±0.09°C
(±0.16°F) |
| K |
-244°C to
+1372°C (-408°F to +2501°F) |
±0.1°C
(±0.17°F) |
| T |
0°C to
+400°C (32°F to 752°F)
-257°C to 0°C (-430°F to +32°F) |
±0.03°C
(±0.05°F)
±0.2°C (±0.36°F) |
| E |
-240°C to
+1000°C (-400°F to +1830°F) |
±0.18°C
(±0.32°F) |
| N |
-245°C to
+1300°C (-410°F to +2370°F) |
±0.10°C
(±0.17°F) |
| R |
-45°C to
+1768°C (-49°F to +3214°F) |
±0.17°C
(±0.31°F) |
| S |
-46°C to
+1768°C (-51°F to +3213°F) |
±0.12°C
(±0.22°F) |
|
Display |
|
Readout
Color
Indicators
Open sensor indication |
5 digits, 7-segment, 14.2 mm (.56")
Red or green LED
Minus sign plus 4 red LED lamps for
relays
Flashes full-scale |
|
Accuracy |
|
Calibration
Overall accuracy at 25º°C
Span tempco
Reference junction accuracy
Span tempco |
NIST
Monograph 125 (IPTS-68)
±0.01% of full span + conformity error
±0.003% of reading/°C
0.5°C, 10°C to 40°C
±0.003% of reading/°C |
|
Electrical |
|
Input resistance
Input current
Max lead resistance
Overvoltage protection
NMR at 50/60 Hz
CMR, DC-60 Hz
CMV, DC-60 Hz |
1 Gohm
100 pA
1 kohm max for rated accuracy
125 Vac
80 dB plus selectable digital filter
120 dB with 500 ohm imbalance
250 Vac from power and earth grounds |
|
A-to-D Conversion |
|
Technique
A-to-D Rate
Output Update
Display Update |
Concurrent Slope (Pat 5,262,780)
60/s at 60 Hz, 50/s at 50 Hz
56/s at 60 Hz, 47/s at 50 Hz
3.5/s at 60 Hz, 3/s at 50 Hz |
|
Power |
|
Voltage, standard
Voltage, optional
Frequency
Power Isolation |
85-264 Vac or 90-300 Vdc (DC operation
not UL approved)
12-32 Vac or 10-48 Vdc
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test |
|
Analog Output (optional) |
|
Output Levels
Current compliance
Voltage compliance
Scaling
Resolution
Isolation |
4-20 mA, 0-20 mA, 0-10V,
-10 to +10V (jumper selectable)
2 mA at 10V ( > 5 kOhm load)
12V at 20 mA ( < 600 Ohm load)
Zero and full scale adjustable from -99999 to +99999
16 bits (0.0015% of full scale)
250V rms working, 2.3 kV rms per 1 min test |
|
Relay Outputs (optional) |
|
Relay
Types
Current Ratings
Output common
Isolation |
2 Form C
contact
relays or 4 Form A contact relays (NO)
2 or 4 Form A, AC/DC solid state relays (NO)
8A at 250 Vac or 24 Vdc for contact relays
130 mA at 140 Vac or 180 Vdc for solid state relays
Isolated commons for dual relays or each pair of quad relays
250V rms working, 2.3 kV rms per 1 min test |
|
Serial Data I/O (optional) |
|
Board Selections
Protocols
Data Rates
Digital Addresses
Isolation |
RS232, RS485, Modbus RS485, USB, USB-to-RS485
converter
Modbus RTU, Modbus ASCII, simpler Laurel ASCII
300 to 19200 bps
247 (Modbus), 31 (Laurel ASCII),
250V rms working, 2.3 kV rms per 1 min test |
|
Environmental |
|
Operating Temp.
Storage Temp.
Relative Humidity
Protection |
0°C to
60°C
-40°C to 85°C
95% at 40°C, non-condensing
NEMA-4X (IP-65) when panel mounted |
|

Application Examples

Operation as a 4-20 mA Transmitter
With the optional analog
output board, Laureate temperature meters can serve as superb, isolated 4-20 mA
transmitters. The analog output is scaled to the display, which is linearized to ºC or
ºF and is exceptionally accurate. The analog output further tracks the high read rate of
the meter, at up to 60 readings
per second at 60 Hz power. Fast update rates are beneficial in many closed-loop and PID
control applications.
Operation as a
Fast Controller
With the dual contact
relay or dual solid state relay output board options, Laureate temperature meters can
serve as extremely fast and accurate ON/OFF controllers
for closed-loop temperature control. Multiple setpoint operating modes are
individually selectable for each relay, as explained in the dual-setpoint controller
section. Relay duty cycles and chatter can be minimized with programmable hysteresis and
time delays. High duty cycles and extremely fast response times are possible with the
solid state relay, which has a typical response time of only 17 ms.
Operation as a Supervisory
Monitor
By using the optional
dual contact relay or dual solid state relay output options, Laureate temperature meters
can monitor processes and provide alarms or shutoffs when these processes exceed normal
limits. A band deviation operating mode can be
selected for each relay, where an alarm is generated whenever the reading is a selected
number of counts above or below the setpoint. Relay operation can be selected as latching
or non-latching. When an alarm or shutdown condition is reached, a latched output will
remain in the alarm condition until it is reset by a front panel pushbutton, via the
serial interface, or via the rear connector.
|

Ordering
Guide
Laureate™ Thermocouple Temperature Panel Meters
Click on the radio buttons to build a model number with pricing (shown below the Ordering Guide).
|